Home > Product > PF(Power fuse)
Power Fuse
- PF(Power fuse)
- Kyung Dong Power Fuse are available for the source-side continuity protection against faults at the transformer, cablefeeder or capacitor bank, and transformer protection against permanent secondary faults(whether the fuse is on the primary or secondary side).
- They are tested according to the latest revisions of ANSIC37.41-1998, and are also designed for sealing the fuse element against ingress of moisture, giving automatic isolation to the open position in the event of the fuse blowing.
- The main characteristics are :
•Full Range Fault Protection with 3-200 Anp. Fusing.
•Full Coordination with other Protective Devices.
•Very Good Performance on Small Over-Current.
Ratings
| Rated Voltage |
25.8kV |
| Rated Frequency |
60Hz |
| Rated Continuous Current |
Fuse Supports |
200A |
| Fuse Units |
3,6,8,10
12,15,20,25
30,40,50,65
80,100,140,200 |
| Rated Max. Interrupting Current |
Symmentrical(r,m,s) |
12.5kA |
| Asymmertical(r,m,s) |
20kA |
| Rated Insulation Level |
Terminal to Ground |
|
| 60Hz Withstand Voltage |
Dry |
1 Min. 70kV |
| Wet |
10 sec. 60kV |
| Impulse Withstand Voltage |
150kV |
| Terminal to Terminal |
60Hz withstand Voltage |
77kV |
| Impules Withstand Voltage |
165kV |